Flow Reports > Magnetic Flow Meter Testing and the Effect of Upstream Chemical Injection on Meter Performance

 

ITRC Flow Report No. F 20-001 

Magnetic Flow Meter Testing and the Effect of Upstream Chemical Injection on Meter Performance

Download Now Download at Digital Commons

 

With funding from the US Bureau of Reclamation, California – Great Basin Region (Region 10), the Cal Poly Irrigation Training & Research Center (ITRC) performed testing on magnetic flow meters to examine issues related to upstream chemical injection. Two sets of tests were completed:

 
The testing revealed that significant flow measurement fluctuations can occur when a chemical is being injected into irrigation water upstream of a magnetic flow meter. This is believed to occur due to non-uniform and rapidly changing fluid properties in the liquid flowing through the meter. While small injections at low to medium frequency resulted in minimal fluctuations, large, continuous injections resulted in significant (≥50%) fluctuations. In fully mixed solutions of chemicals and irrigation water, fluctuations were negligible.The magnetic flow meters that were tested are described in Table 1. The layout, procedures, and results of both tests are found in the body of this report.

 

Styles, S., S. Layous, and J. Evans 2020. Magnetic Flow Meter Testing and the Effect of Upstream Chemical Injection on Meter Performance. Irrigation Training & Research Center, California Polytechnic State University, San Luis Obispo. ITRC FLow Report No. F 20-001.